03119 rev. 07Installer ManualVENTILATION SYSTEMSvänEE Canadian Model Numbers1001 ERV1001 HRV2001 ERV2001 HRV*Broan U.S.A. Model NumbersHRV100HHRV200HE
105. Installation (cont’d)Use the table below to ensure that the ducts you intend to install will be carrying air flows at or under the recommended va
There are two methods for connecting the unit to the furnace:Method 1: Supply side connection• Cut an opening into the furnace supply duct at least 18
125. Installation (cont’d)5.4.3 Simplified installation (Volume Ventilation) (as illustrated in Section 4.3)There are two methods (figures 12 and 13)
Insulated flexible ductUse the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to outside and fresh a
Make a water trap loop in the tubeto prevent the unit from drawingunpleasant odors from the drainsource. Make sure this loop is locatedBELOW the “T” a
15VT1W model(U.S.A.)6.1 MAIN CONTROLS6. Control DevicesCONDENSATION CONTROLAIR SUPPLY CONTROLMIN.MAX.OFFAIREXCHANGE-20°C-4° F-5° C23°F5°C41°FCOMFORTZO
6.4 MAIN AND OPTIONAL CONTROLS AVAILABLE FOR YOUR UNIT6.3 OTHER FEATURESFURNACE INTERLOCK (for forced air heating system)The furnace fan can be interl
7.2 INSTALLATION OF THE MAIN CONTROL7. Installation of the Controls7.1 DIMENSIONS AND SPECIFICATIONS (MAIN CONTROLS)5" (127 mm)VC0016A5" (12
7.2 INSTALLATION OF THE MAIN CONTROL (CONT’D)187.2.3 Dehumidistat, DH100W, VT1W, and VT2W Main Controls Installation1- Determine the location of the c
197.3 ELECTRICAL CONNECTION TO OPTIONAL CONTROLS987654321OLOCI1 4 72 5 83 6 9J3MAIN PC BOARDPUSH-BUTTON SWITCHES(HRV100H and HRV200H :5 swi
2Table of Contents1. SERVICE ...
W R GYWRGCY987654321UNIT CONTROL CONNECTORTHERMOSTATTERMINALSFOUR WIRESI OC OL Y R G BF FJ3TWO WIRESheating onlyFURNACE24-VOLTTERMINAL BLOCKTWO WIR
COLOR CODEBK BLACK NC NO CONNECTIONBL BLUE O ORANGEBN BROWN R REDG GREEN W WHITEGY GREY Y YELLOW218. Wiring DiagramsA1M1M2K1RELAYK2RELAYK5RELAYFANMOTO
22A1M1M2K1RELAYK2RELAYK5RELAYFANMOTORDAMPERMOTORNEUTRALMEDNCHIGHLOWJ1 6J1 3J1 4J1 9ELECTRONIC ASSEMBLYS1120V 60HzFROM MAINJ1 2J1 1J1 8VE0040ABKGRNO
23WHAT YOU NEED TO BALANCE THE UNIT• A magnehelic gauge capable of measuring 0 to 0.25 inch of water (0 to 62.5 Pa) and 2 plastic tubes.• Two ”Flow Me
24BALANCING PROCEDURE1. Set the unit to high speed.Make sure that the furnace blower is ON if the installation is in any way connected to the ductwor
At its very start-up, the Platinumcontrol will perform a bootingsequence before being ready tooperate. The booting sequence isdone when the hour displ
20/40/60-MINUTE PUSH-BUTTON TIMER:(Not available for HRV100H and HRV200Hmodels.)Activate the push-button. Within 2 seconds,push one time for 20 minute
27Start-up troubleshooting:NOTE: Inspect the unit before proceeding with these steps.12. TroubleshootingPROBLEMS POSSIBLES CAUSES YOU SHOULD TRY THIS
13. ReferencesR 2000• HVI, “Installation Manual for Heat Recovery Ventilators”, 1987 edition.• ASHRAE 1984 Systems Handbook, chapter 11, “Air Distribu
31.1 3-D DRAWING6123457891011121314151617181920212232323242526VL0016DAMPER ASSEMBLY (REAR VIEW)About this ManualThis manual uses the following symbols
4Canada: Tel: 1-888-908-2633 (for distributors only)U.S.A.: Tel: 1-800-637-1453No. Description1001 1001 2001 2001 HRV ERV HRV ERVHRV ERV HRV ERV 100H
ANCHORAGEWHITEHORSEJUNEAUHAY RIVERYELLOWKNIFEPrince RupertGRANDE PRAIRIEFORT MCMURRAYZONE AFORT SMITHEDMONTONPRINCE ALBERTSASKATOONJASPERKAMLOOPSCALGA
63.3 DEFROST CYCLE TABLE3.1 AIR DISTRIBUTION (NORMAL OPERATION)3.2 AIR DISTRIBUTION (DEFROST MODE)3. Technical DataVF0013FRESH AIRFROMOUTSIDESTALE AIR
713¾" (349mm)20"(508mm)6" (152mm)2½" (63mm)30¼" (768mm)VK0040A19" (483mm)20"(508mm)6" (152mm)30¼" (768mm)
84. Typical Installation(Primarily for homes with radiant hot water or electric baseboard heating. See figure 1.)Moist, stale air is exhausted from th
95. InstallationChoose an appropriate location for the unit:• Within an area of the house where the temperature is kept above 10°C / 50°F and below 40